Fan Tech FKD Series Inline Centrifugal Fan Specifications

Dimensional Data
Model A C D E Weight
FKD 8XL 8 12 1/2 15 1/2 7 16 lbs
FKD 10 10 12 1/2 12 1/2 7 16 lbs
FKD 10XL 10 14 15 8 22 lbs
FKD 12 12 14 12 1/2 8 21 lbs
FKD 14 14 17 7/8 17 1/4 1 -
FKD 14XL 14 19 3/4 20 1/4 1 1/2 -
FKD 16 16 19 3/4 18 3/4 1 1/2 -
FKD 16XL 16 22 1/8 23 1/4 1 1/4 -
FKD 18 18 22 1/8 21 3/4 1 1/4 -
FKD 18XL 18 22 1/4 29 1/4 2 -

All dimensions in inches.
Dimensional Data
Model A A1 A2 C D E F
FKD 12XL 12 12 14 17 7/8 18 7/8 7/8 1 5/8

All dimensions in inches.
Performance Data
Fan
Model
RPM Volts Max.
Watts
Max.
Amps
0" .125" .25" .375" .5" .75" 1.0" 1.25" 1.5" 2.0" Max.
Ps
Duct
Dia.
*Sones
FKD 8XL 2700 115 327 2.99 836 799 761 720 680 595 499 393 286 - 2.59" 8" 14.1
FKD 10 2700 115 329 3.01 910 873 836 795 752 653 547 432 342 - 2.60" 10" 15.3
FKD 10XL 2850 115 529 4.84 1266 1226 1187 1147 1100 1006 911 810 696 460 3.08" 10" 21
FKD 12 2900 115 531 4.86 1305 1266 1228 1189 1145 1054 948 833 712 479 3.08" 12" 23
FKD 12XL 1700 115 500 4.80 2016 1920 1832 1746 1649 1423 1066 606 - - 1.52" 12" 18.7
FKD 14 1700 115 495 4.76 2156 2061 1965 1868 1764 1520 1193 623 - - 1.52" 14" 18.4
FKD 14XL 1550 115 738 7.12 2619 2517 2416 2303 2180 1936 1662 1294 843 - 1.94" 14" 19
FKD 16 1600 115 742 6.39 2952 2831 2707 2580 2445 2144 1804 1306 774 - 1.90" 16" 18.5
FKD 16XL 1600 115 1421 12.40 4274 4144 4014 3880 3743 3452 3137 2794 2379 1242 2.42" 16" 25
FKD 18 1600 115 1411 12.04 4448 4992 4130 3991 3871 3583 3239 2843 2380 1231 2.51" 18" 24
FKD 18XL 1700 460/3 2208 3.75 6236 6115 5995 5874 5754 5500 5199 4909 4602 3703 3.42" 18" 32

Performance shown is for installation type D - Ducted inlet, Ducted outlet. Speed (RPM) shown is nominal. Performance is based on actual speed of test. Performance ratings do not include the effects of appurtenances in the airstream.
* The sound ratings shown are loudness values in fan sones at 5ft. (1.5m) in hemispherical free field calculated per AMCA Standard 301. Values shown are for installation Type D: ducted inlet fan sone levels. Ratings do not include the effect of duct end correction. All sone values shown are calculated at 0.5" (static pressure in inches W.G.).